Voltage Drop Calculator

Estimate feeder voltage drop using conductor size, current, run length and conductor material.

Estimated voltage drop Enter values
Preliminary size only: the built-in current-density method is a screening calculation, not a replacement for an IS/IEC or manufacturer ampacity table. Final cable size must satisfy ampacity, voltage drop, short-circuit withstand and protection requirements.

How this calculator works

This quick calculator estimates conductor resistance from material resistivity and cross-sectional area.

1 phase: Voltage drop = 2 × I × L × R.

3 phase: Voltage drop = sqrt(3) × I × L × R.

Cable reactance is not included. For large AC cables, long runs or critical design, use the manufacturer's R and X values and the applicable standard method.

Example

Long cable runs and smaller conductor sizes produce larger voltage drop for the same current.

Source and engineering note

BIS lists IS 732:2019 as the Code of Practice for Electrical Wiring Installations and IS 8130:2013 for conductors used in insulated electric cables and flexible cords. IEC 60364-5-52 covers selection and erection of wiring systems, including current-carrying capacity and voltage drop.

CalcSetu's cable tools are preliminary engineering estimates. Final cable selection must be verified against the actual cable manufacturer's current-carrying-capacity table, installation method, ambient temperature, grouping, harmonics, protective device and short-circuit withstand.

Bureau of Indian Standards - IEC 60364-5-52

Last reviewed: 27 August 2026.

Frequently asked questions

Does this include reactance?

No. It is a simplified resistive estimate. Detailed AC voltage drop can require both resistance and reactance.

Why does temperature matter?

Copper and aluminium resistance increases as conductor temperature rises.

Is one-way length used?

Yes. The formula handles the return path factor for single-phase and sqrt(3) relationship for three-phase.